U is a “height address”
The rack’s posts are numbered 1, 2, 3… in U from the bottom, and positions are given in U, as in “mount the server in 20–21U.” 1U = 44.45 mm, so a 2U server is about 89 mm. Each U has three holes, and you fit “cage nuts” into the square holes to fasten screws. Many servers today use rails that click in without screws.
With Dell PowerEdge, for example, the R660 is 1U and the R760 is 2U. A 2U chassis has more room inside, so it can hold more disks or take GPUs and expansion cards. A 1U saves space, but it cools itself by spinning small fans fast, so it tends to be loud.
Choose a matching depth too
The width is a common 19 inches, but depth varies. Many servers are 70–80 cm deep, and you need room behind them for cables and power strips, so data centers commonly use racks 1000–1200 mm deep. That’s why a 2U server sometimes won’t fit in a small 19-inch rack meant for home use.
Breathe in at the front, out the back
Most servers are built to pull in cool air at the front and blow hot air out the back. So racks are lined up front to front, making the aisle on the front side a path for cool air (the cold aisle) and the aisle on the back side a path for hot air (the hot aisle).
Empty slots are covered with blanking panels because gaps let hot air from the back loop around to the front, and the servers end up breathing their own exhaust. A single gap can raise the temperature of the servers above and below it.
Split power into two feeds
The power strip inside a rack is called a PDU (Power Distribution Unit). Servers often have two power supply units: the first goes to the PDU on feed A and the second to the PDU on feed B — separate feeds. If one feed stops for work or a fault, the server keeps running on the other alone.
Another important point is the cap on how much power one rack can use. Contracts often fix it, like “up to 6 kVA per rack,” and since AI GPU servers now draw several kW each, it often happens that “there’s free U, but not enough power to add more.”
Record what’s mounted at which U of each rack in a “rack elevation diagram.” If a call comes in at midnight saying “the server at 15U has a red light,” the diagram and the U numbers lead even someone visiting that rack for the first time straight to the right device.
Practice questions
Four-choice questions in the style of Japan’s Fundamental Information Technology Engineer Examination. Tap below to see the answer.
Q1Which is the correct height of 1U?
- AAbout 10 mm
- BAbout 25.4 mm
- CAbout 44.45 mm
- DAbout 100 mm
Show the answer and explanation
Answer: C1U = 1.75 inches = 44.45 mm. 25.4 mm is the length of 1 inch.
Q2What is the main purpose of fitting blanking panels to empty slots in a rack?
- ATo keep dust from collecting
- BTo make it look tidy
- CTo keep hot air from the back looping around to the front
- DTo make the rack lighter
Show the answer and explanation
Answer: CWith gaps, hot air blown out the back loops around to the front and the servers breathe it in. Covering them means the servers draw in only cool air.
Q3What is the most appropriate way to connect a server with two power supply units?
- AConnect both to the same power strip
- BConnect them to power strips on separate feeds
- CConnect only one and leave the other unplugged
- DConnect them to an extension cord outside the rack
Show the answer and explanation
Answer: BConnected to separate feeds (A and B), the server keeps running on one if the other stops. Plug both into the same strip, and both stop the moment that strip does.
- U is the height address in a rack; 1U = 44.45 mm. Check depth too
- Breathe in at the front, out the back. Fill gaps with blanking panels
- Split power across two PDU feeds. These days the power cap often comes first