5-min deep dive

Rack power in depth: kVA math, redundancy and heat

How many devices fit in a rack is often decided by power before height. How power capacity is set, calculating the count, two power feeds and the 80% rule, and how electricity becomes heat.

Reading time: about 5 min

← Start with the 1-min version
34U freePower 10/15 kW1 GPU server8U freePower 13.6/15 kW34 1U servers30U freePower 3.6/15 kW12 switches
Every rack is capped at 15 kW. One GPU server uses about 10 kW, so a second one won’t fit

How is power capacity set?

Power reaches a rack through power strips (PDUs). Behind each PDU is a breaker in the distribution board, and its size sets the cap on how much power can flow. When you rent space in a data center, the contract is written as “up to so many kVA per rack.”

kVA is the “apparent” size of the power, and kW is the power that actually does work. For server power supplies, kVA and kW are nearly the same (the power factor is close to 1), so they’re often treated as roughly equal in calculations.

Calculate how many fit

Here’s what happens if you fill a rack capped at 15 kW with only one kind of device. Of the count limited by power and the count limited by height (42U), the smaller one is the answer.

DevicePower per unitHeightFits in 15 kWHeight usedFree
GPU serverabout 10 kW8U18U34U
2U serverabout 0.75 kW2U1836U6U
1U serverabout 0.4 kW1U3434U8U
Switchabout 0.3 kW1U12 (only as many as needed)12U30U

For GPU servers, power limits the count to 1, leaving 34U of height to spare. For 1U servers, power and height run out at about the same time. This calculation is why the more power a device draws, the emptier its rack looks.

Two power feeds and “up to 80%”

Important servers have two power supplies, and racks normally get two power feeds, “A” and “B.” The design keeps total power within what one feed can supply, so that if one feed fails, the other alone can run every device.

On top of that, to keep breakers from tripping, it’s common to stay at about 80% rather than the full cap. A 15 kW rack actually uses about 12 kW, so a few fewer devices fit than the math on paper suggests.

Nearly all electricity becomes heat

Almost all the electricity a server uses ends up as heat. A rack drawing 10 kW keeps giving off as much heat as a 10 kW electric heater. So power capacity is set together with how much heat the site can cool.

In AI-oriented data centers, more and more sites add “liquid cooling,” which cools with water instead of air, on top of thick power feeds, so a single rack can draw tens of kW to over 100 kW.

Field note: “there’s space, but you can’t put anything there”

When you go to look at a new rack, you may be told “nothing more can go in” even though it’s more than half empty. The reason is usually power capacity.

In design, add up the power of the devices before you count U. Adding up the catalog maximums makes it too strict, so also check typical actual usage.

Practice questions

Four-choice questions in the style of Japan’s IT Passport and Fundamental Information Technology Engineer exams. Tap below to see the answer.

Q1GPU servers drawing about 10 kW each are placed in a rack with a power capacity of 15 kW. Ignoring other equipment, how many can it hold?

  • A1
  • B2
  • C5
  • D42
Show the answer and explanation

Answer: ATwo would be about 20 kW, over the 15 kW cap. Even if the rack has height to spare, you can’t add a device without enough power.

Q2Sometimes you can’t add a server even though the rack has free height (U). What is the most appropriate reason?

  • AThe rack’s power capacity is near its cap
  • BThe rack’s height is fixed at 42U
  • CThe server’s OS is old
  • DThe floor is a raised floor
Show the answer and explanation

Answer: AOnce the available power is used up, you can’t add equipment even if there’s space. High-power devices make this more likely.

Q3Which statement about the power a server uses is correct?

  • AMost of the power used becomes heat, so the more power, the more cooling is needed
  • BThe power used leaves as light, so no cooling is needed
  • CThe more power a server uses, the less heat it gives off
  • DPower and heat are unrelated
Show the answer and explanation

Answer: AAlmost all the electricity a server uses ends up as heat. That’s why power capacity and cooling are considered together.

Summary
  • A rack’s power capacity is set by its breakers, PDUs and how much heat can be cooled
  • The number that fits is the smaller of the “power” limit and the “height” limit
  • Make power redundant with two feeds, and use up to about 80%
  • Nearly all electricity becomes heat, so plan power and cooling together